The Series CCS Current Switches are ideal for monitoring the operating status of fans, pumps, and motors. These self-powered switches can be hung or tied directly to cables or wires. For use on existing installations, split core models can be installed without disconnecting cables. LED indicators provide a visual confirmation that the current is flowing through the core. Both fixed and adjustable set points are available. The adjustable models utilize a potentiometer to easily adjust the set point.
See less
Amperage Range: 0 to 200 A AC
Maximum Switch Rating: For fixed set point models: 0.3 A @ 135 VAC/DC; For adjustable set point models: 1 A @ 240 VAC
Output: Normally open, NPN
Power Requirements: None, self-powered
Temperature Limits: -22 to 158ºF (-30 to 70ºC)
Humidity Limits: 0 to 95% (non-condensing)
Isolation Voltage: 2000 V
Frequency: 40 to 400 Hz
Enclosure Rating: UL, 94 V-O flammability rated, ABS plastic housing
Approvals: CE, cUL, UL