Sensing Element - Various thermistors and RTDs
Sensor Accuracy - Thermistors: ±0.2°C (±0.36°F), 0 to 70°C (32 to 158°F) Platinum RTD’s: ±0.3°C (±0.54°F) at 0°C (32°F), Nickel RTD’s: ±0.4°C (±0.72°F) at 0°C (32°F)
Operating Conditions - 0-50 °C (32-122 °F), 0-95 %RH non-condensing
Wiring Connections - Screw terminal block (14 to 22 AWG) Sensor only - Pigtail, 2 or 3 wire
Enclosure - Wall mount enclosure,
White ABS - IP30 (NEMA 1) 84 w x 119 h x 29 d mm (3.3” x 4.7” x 1.15”)
-TXRC SERIES
.
Sensor - 1000 ohm or 100 ohm Platinum RTD
Sensor Accuracy - 0.3°C (±0.54°F) @ 0°C (32°F)
Output Signal - 4-20mA current loop, 0-5 vdc, or 0-10 Vdc (factory configured)
Transmitter Accuracy - ±0.1% of span, including linearity
4-20 mA loop Power Supply - 15-35 Vdc or 22-32 Vac
Minimum Current Loop - 2 mA nominal (occurs with shorted sensor)
Maximum Loop Current - 22.5 mA nominal (occurs with open sensor)
Maximum Loop Load - >600 ohms
-HRC SERIES
-HTRC SERIES